The MAXQ3180 is a dedicated electricity measurement front-end that collects and calculates polyphase voltage, current, power, energy, and many other metering
and power-quality parameters of a polyphase load. The computed results can be retrieved by an external master through the on-chip serial peripheral interface
(SPI™) bus. This bus is also used by the external master to configure the operation of the MAXQ3180 and monitor the status of operations.
The MAXQ3180 performs voltage and current measurements using an integrated ADC that can measure up to seven external differential signal pairs. An eighth differential signal pair is used to measure the die temperature. An internal amplifier automatically adjusts the current channel gain to compensate for low-current channel-signal levels.
Key Features
Supports IEC 60687, IEC 61036, and IEC 61268 Standards
Compatible with 3-Phase/3-Wire, 3-Phase/4-Wire, and Other 3-Phase Services
0.1% Active Power and Energy Linearity Error
0.2% Reactive Power and Energy Linearity Error
0.2% Apparent Power and Energy Linearity Error
0.5% Linearity Errors for RMS Voltage and RMS Current
Neutral Line Current Measurement
Line Frequency (Hz)
Power Factors
Voltage Phasor Angles
Phase Sequence Indication
Phase Voltage Absence Detection
Voltage and Current Harmonic Measurement
Fundamental and Total Power and Energy
Two Pulse Outputs: Configurable for Active, Reactive, and Apparent Powers
Programmable Pulse Widths
Programmable No-Load Current Threshold
Programmable Meter Constants
Programmable Thresholds for Undervoltage and Overvoltage Detection
Programmable Threshold for Overcurrent Detection
Amp-Hours in Absence of Voltage Signals
On-Chip Digital Temperature Sensor
Precision Internal Voltage Reference 1.23V (30ppm/°C typical), Also Supports An External Voltage Reference
Active Power and Energy of Each Phase and Combined 3-Phase (KWh), Positive and Negative
Reactive Power and Energy of Each Phase and Combined, Positive and Negative
Apparent Power and Energy of Each Phase and Combined 3-Phase
Supports Software Meter Calibration
Up to 3-Point Multipoint Calibration to Compensate for Transducer Nonlinearity
Power-Fail Detection
Bidirectional Reset Input/Output
SPI-Compatible Serial Interface with Interrupt Request (Active-Low IRQ) Output
Notes: **This pricing is BUDGETARY, for comparing similar parts. Prices are in
U.S. dollars and subject to change. Quantity pricing may vary
substantially and international prices may differ due to local
duties, taxes, fees, and exchange rates. For volume-specific prices
and delivery, please see the price and availability page
or contact an authorized distributor.